CFD-01 – A0 (A60) E120S Fire damper

Designed to operate in the most arduous conditions and extremes of climate and temperature, Flamgard Calidair dampers have a proven record of reliability and high performance across multiple industries.

Request a Quote

Overview

  • Certified IMO Annex FTP 1, Part 3 certified by Lloyds Register of Shipping, DNV, ABS and BV.
  • Type tested/approved and compliant to EN1366-2 Fire Resistant to E (Integrity) S (Smoke) and I (Insulation) from 30 to 120 minutes. (Patented).
  • BS 15650 accredited.
  • Type tested/approved for Hydrocarbon applications H0-H120.
  • Type tested/approved BS476
  • Type tested/approved GOST R 55301-2009. (Patented).
  • NORSOK case and blade leakage compliant.
  • Case and Blade leakage compliant to EN 1751.
  • Independent SIL2 Certified
  • ATEX Compliant.
  • ISO 9001:2015 accredited
  • Independent Pressure Drop Tested
  • Independent Noise Tested
  • Independent Seismic and Blast tested

Specification

The type CFD-01 Fire and Smoke Dampers are utilised in ventilation systems to prevent the passing and spread of fire and smoke between designated divisions. The Flamgard Calidair Fire Damper is designed for bolting to steel bulkheads & decks, fixing to walls or floors or connecting directly to ductwork. All bolted connections are made via integral bolted angle flanges.
The damper has been successfully tested to global international standards highlighted above.

Dimensions

Casing

The damper casing is formed from 3.0 mm thick sheet steel into a rigid channel section to ensure proper alignment of blades and shafts. Damper Units in excess of 3000mm width or height shall be manufactured as a multiple unit assembly. Where circular dampers or dampers with width or height dimensions less than 150 mm are required, additional spigot adaptors are used which increase the damper insertion length from 300 to 400 mm.

Blades

The blades are a formed double-skin aerofoil section of 1.5 mm sheet metal which operate on the ‘Firelock’ principle creating a 3-pass labyrinth between the blades which fire cannot penetrate. Blade stops at the top and bottom of the casing and sprung side seals provide excellent low leakage characteristics. Dependent on market sector or required certification of the Damper additional patented sealing and blade materials are utilized.

Shafts

Continuous Ø 19.05 mm with blades plug welded at each end.

CFD-01 General Drawings

Material and Finishing

Part Material Finishing
Case Mill Galvanised Mild Steel Mill Finish
Case Stainless Steel – 1.4307 (304L)
Stainless Steel – 1.4404 (316L)
Typically 2B finish
Blades Mill Galvanised Mild Steel Mill Finish
Blades Stainless Steel – 1.4307 (304L)
Stainless Steel – 1.4404 (316L)
Typically 2B finish
Shafts Stainless Steel – 1.4307 (304L)
Stainless Steel – 1.4404 (316L)
Bearings Oil Impregnated Sintered Bronze
(other options available on request)

Product Models and Accessories

Flamgard Calidair CFD-01 Fire and Smoke Dampers are available with the following actuators:

  • Manually operated damper with a spring pack and fusible link.
  • Pneumatic spring return actuator.
  • Electronic spring return actuators with a voltage range between 24V to 430V. Including models that can be used in Ex areas and hazardous locations.
  • Electro-hydraulic actuators

Damper control systems can be mounted within an enclosure to protect them from the elements and mechanical damage.
Dampers can be fitted with a with a range of controls components for safe and hazardous areas including suitable IP ratings where required.
For available options please contact sales team for more information.

Operation Principle

Under normal operation, Fire Dampers will remain in the open position allowing for the ventilation of the associated areas. By definition, Fire Dampers must fail-safe closed to protect the rating of the fire division. This is typically achieved using a spring return system ensuring the damper closes even on loss of power.

Automatic operation in the event of a temperature rise in ductwork:

  • The fusible link will release and thus allowing the mechanical spring pack to close the dampers blades.
  • The fusible link releases and operating pressure will be cut off to the pneumatic actuator, thus causing the damper blades to close fully.
  • The fusible link releases and operating voltage will be cut off to the electric actuator, thus allowing the spring to close the damper blades fully.

Additional operations may include

  • Remote operation of the fire damper.
  • Local operation of the fire damper.
  • Remote indication of the fire dampers status.
  • Local indication of the fire dampers status.
  • Facility for automatic operation from fire or gas detection systems.
  • Facility for ‘black start’ operation.

Weights

Please note the below table gives bare shaft damper weights only at the given square dimensions. Weights for specific sizes are issued on the quotation document.

Damper size (mm) Est. weight
Width/Dia. Height Depth
150 150 300 10 kg
200 200 300 12 kg
250 250 300 15 kg
300 300 300 20 kg
350 350 300 23 kg
400 400 300 26 kg
450 450 300 31 kg
500 500 300 35 kg
550 550 300 39 kg
600 600 300 44 kg
650 650 300 48 kg
700 700 300 53 kg
750 750 300 59 kg
800 800 300 64 kg
850 850 300 68 kg
900 900 300 76 kg
950 950 300 81 kg
1000 1000 300 86 kg

Installation

Dampers are typically provided with integral drilled flanges that allow for bolting to ductwork, structural divisions, wall sleeves and similar. Flanges and drillings can be to Flamgard standard or customer specification.
Dampers can be fitted in any orientation with airflow in either direction.
Installation and maintenance instructions can be provided with each damper delivery.